Alternatively, you can contact us like this:
DRB 3 PHASE SERIES
The DIN-Rail power supplies in the DRB series are part of TDK-Lambda's industrial heritage. They can be used in many applications, ranging from conventional switch cabinets and decentralised machinery and systems, to renewable energy and charging solutions. The series covers the popular output voltages of 12, 24, 48 and 72 volts, and users can operate them, both with AC or DC voltage.
The DRB's high operating efficiencies, the use of high-quality electrolytic capacitors and the integration of a gas discharge tube provide maximum system up-time. Special models featuring conformal coating are available for use in challenging environments containing corrosive gases. Overall the DRB 3 phase series offer an excellent balance between functionality and price.
A very short inrush current AC combined with very low switch-on energy prevents nuisance tripping of circuit breakers. This reduces disturbances during commissioning and system restarts.
Starting into a capacitive load poses a challenge for many power supplies. Thanks to comprehensive boost power capability of 150 percent for several seconds, these applications get reliably started.
DRB models of the same voltage and current can be connected in parallel to provide higher power. Activating the parallel mode will distribute the load current between the power supplies. This reduces thermal stress and increases the longevity in the field.
Special models with coated circuit boards are suitable for use in polluted environments containing corrosive gases, dust or salt mist. This makes them a reliable and long-lasting source of power.
FEATURES AND BENEFITS
PRODUCT VIEWER
All products are available as -A0 (screw terminal) and -A1 (push-in terminal) versions.
TECHNICAL DATA
DRB120-12-3-XX | DRB120-24-3-XX | DRB240-24-3-XX | DRB240-48-3-XX | ||
---|---|---|---|---|---|
Output voltage | nom. | 12VDC | 24VDC | 24VDC | 48VDC |
Adjustment range | nom. | 11.4.. 15VDC | 22.5.. 29VDC | 22.5.. 29VDC | 45.. 56VDC |
Output current | nom. | 10A | 5A | 10A | 5A |
Boost current 1 | max. | 12A / continous | 6A / continuous | 12A / 300s | 6A / 300s |
Boost current 2 | max. | 14.5A / 600s | 7.5A / 600s | 15A / 60s | 7.5A / 60s |
Overload behaviour | Constant current + Intermittent mode (Hiccup) | ||||
Mains frequency | nom. | 50/60Hz | |||
Input voltage AC | nom. | 3x380 .. 500VAC (-10/+15%) | |||
Input voltage DC | nom. | 530 .. 675VDC (-15/+20%) | |||
Inrush current AC 1 | max. | 25 / 30A <2ms | 25 / 30A <3ms | ||
Inrush energy AC 1 | max. | 0.3 / 0.6A2s | 0.3 / 0.8A2s | ||
Inrush current DC 2 | max. | 38 / 41 / 53A <2ms | 39 / 47 / 60A <3ms | ||
Inrush energy DC 2 | max. | 0.7 / 0.8 / 1.3A2s | 1.1 / 1.5 / 2.3A2s | ||
Output power | nom. | 120W | 240W | ||
Boost power 1 | max. | 144W / continuous | 288W / 300s | ||
Boost power 2 | max. | 174W / 600s | 360W / 60s | ||
Power factor | typ. | 0.50 | 0.60 | ||
Conversion efficiency AC 1 | min. | 89.4 / 89.1% | 91.3 / 91.2% | 93.1 / 93.2% | 93.8 / 94% |
Power losses AC 1 | max. | 14.2 / 14.7W | 11.4 / 11.6W | 17.8 / 17.5W | 15.9 / 15.3W |
No-load consumption AC 1 | max. | 1.7 / 2.1W | 1.7 / 2.1W | 1.6 / 2.0W | 1.9 / 2.3W |
Conversion efficiency DC 2 | typ. | 92.1 / 92.0 / 90.9% | 92.4 / 92.2 / 91.4% | 94.7 / 94.8 / 94.5% | 95.1 / 95.1 / 94.9% |
Power losses DC 2 | typ. | 10.3 / 10.4 / 12.0W | 9.9 / 10.2 / 11.3W | 13.4 / 13.2 / 14.0W | 12.4 / 12.4 / 12.9W |
No-load consumption DC 2 | max. | 1.8 / 2.2 / 2.8W | 1.8 / 2.2 / 2.6W | 2.0 / 2.3 / 3.0W | 1.9 / 2.3 / 3.0W |
Service lifetime 1 | min. | 162,000 / 142,000hrs | 184,000 / 162,000hrs | 82,000 / 78,000hrs | 94,000 / 90,000hrs |
Service / Early life MTBF 3 | min. | 1.8M / 0.79M hrs | |||
Ambient operating temperature | max. | -25 .. +70°Camb (-13 .. +158°Famb) | |||
Ambient operating temperature | nom. | -25 .. +55°Camb (-13 .. +131°Famb) | |||
Power derating | min. | 2.0W/°Camb (1.11W/°Famb) |
0.8W/°Camb (0.44W/°Famb) |
2.4W/°Camb (1.33W/°Famb) |
2.6W/°Camb (1.44W/°Famb) |
Operating altitude | nom. | 3000mASL (9842ftASL) | |||
Operating altitude | max. | 6000mASL (19685ftASL) 4 | |||
Ingress protection degree | IP 20 | ||||
Radiated noise emission | Class B | ||||
Conducted noise emission | Class B | ||||
Width x Height x Depth | max. | 55 x 129 x 138.2mm (2 11/64 x 5 5/64 x 5 7/16 inch) |
|||
Weight | 660g (1.46lb) | 780g (1.72lb) | |||
Certifications (CB, UL, UR) | IEC/EN/UL/CSA 61010-1, 61010-2-201, 62368-1 (Ed.3) |
DRB120-12-3-XX | ||
---|---|---|
Output voltage | nom. | 12VDC |
Adjustment range | nom. | 11.4.. 15VDC |
Output current | nom. | 10A |
Boost current 1 | max. | 12A / continuous |
Boost current 2 | max. | 14.5A / 600s |
Overload behaviour | Constant current + Intermittent mode (Hiccup) | |
Mains frequency | nom. | 50/60Hz |
Input voltage AC | nom. | 3x380 .. 500VAC (-10/+15%) |
Input voltage DC | nom. | 530 .. 675VDC (-15/+20%) |
Inrush current AC 1 | max. | 25 / 30A <2ms |
Inrush energy AC 1 | max. | 0.3 / 0.6A2s |
Inrush current DC 2 | max. | 38 / 41 / 53A <2ms |
Inrush energy DC 2 | max. | 0.7 / 0.8 / 1.3A2s |
Output power | nom. | 120W |
Boost power 1 | max. | 144W / continuous |
Boost power 2 | max. | 174W / 600s |
Power factor | typ. | 0.50 |
Conversion efficiency AC 1 | min. | 89.4 / 89.1% |
Power losses AC 1 | max. | 14.2 / 14.7W |
No-load consumption AC 1 | max. | 1.7 / 2.1W |
Conversion efficiency DC 2 | typ. | 92.1 / 92.0 / 90.9% |
Power losses DC 2 | typ. | 10.3 / 10.4 / 12.0W |
No-load consumption DC 2 | max. | 1.8 / 2.2 / 2.8W |
Service lifetime 1 | min. | 162,000 / 142,000hrs |
Service / Early life MTBF 3 | min. | 1.8M / 0.79M hrs |
Ambient operating temperature | max. | -25 .. +70°Camb (-13 .. +158°Famb) |
Ambient operating temperature | nom. | -25 .. +55°Camb (-13 .. +131°Famb) |
Power derating | min. | 2.0W/°Camb (1.11W/°Famb) |
Operating altitude | nom. | 3000mASL (9842ftASL) |
Operating altitude | max. | 6000mASL (19685ftASL) 4 |
Ingress protection degree | IP 20 | |
Radiated noise emission | Class B | |
Conducted noise emission | Class B | |
Width x Height x Depth | max. | 55 x 129 x 138.2mm (2 11/64 x 5 5/64 x 5 7/16 inch) |
Weight | 660g (1.46lb) | |
Certifications (CB, UL, UR) | IEC/EN/UL/CSA 61010-1, 61010-2-201, 62368-1 (Ed.2) |
DRB120-24-3-XX | ||
---|---|---|
Output voltage | nom. | 24VDC |
Adjustment range | nom. | 22.5.. 29VDC |
Output current | nom. | 5A |
Boost current 1 | max. | 6A / continuous |
Boost current 2 | max. | 7.5A / 600s |
Overload behaviour | Constant current + Intermittent mode (Hiccup) | |
Mains frequency | nom. | 50/60Hz |
Input voltage AC | nom. | 3x380 .. 500VAC (-10/+15%) |
Input voltage DC | nom. | 530 .. 675VDC (-15/+20%) |
Inrush current AC 1 | max. | 25 / 30A <2ms |
Inrush energy AC 1 | max. | 0.3 / 0.6A2s |
Inrush current DC 2 | max. | 38 / 41 / 53A <2ms |
Inrush energy DC 2 | max. | 0.7 / 0.8 / 1.3A2s |
Output power | nom. | 120W |
Boost power 1 | max. | 144W / continuous |
Boost power 2 | max. | 174W / 600s |
Power factor | typ. | 0.50 |
Conversion efficiency AC 1 | min. | 91.3 / 91.2% |
Power losses AC 1 | max. | 11.4 / 11.6W |
No-load consumption AC 1 | max. | 1.7 / 2.1W |
Conversion efficiency DC 2 | typ. | 92.4 / 92.2 / 91.4% |
Power losses DC 2 | typ. | 9.9 / 10.2 / 11.3W |
No-load consumption DC 2 | max. | 1.8 / 2.2 / 2.6W |
Service lifetime 1 | min. | 184,000 / 162,000hrs |
Service / Early life MTBF 3 | min. | 1.8M / 0.79M hrs |
Ambient operating temperature | max. | -25 .. +70°Camb (-13 .. +158°Famb) |
Ambient operating temperature | nom. | -25 .. +55°Camb (-13 .. +131°Famb) |
Power derating | min. | 0.8W/°Camb (0.44W/°Famb) |
Operating altitude | nom. | 3000mASL (9842ftASL) |
Operating altitude | max. | 6000mASL (19685ftASL) 4 |
Ingress protection degree | IP 20 | |
Radiated noise emission | Class B | |
Conducted noise emission | Class B | |
Width x Height x Depth | max. | 55 x 129 x 138.2mm (2 11/64 x 5 5/64 x 5 7/16 inch) |
Weight | 660g (1.46lb) | |
Certifications (CB, UL, UR) | IEC/EN/UL/CSA 61010-1, 61010-2-201, 62368-1 (Ed.3) |
DRB240-24-3-XX | ||
---|---|---|
Output voltage | nom. | 24VDC |
Adjustment range | nom. | 22.5.. 29VDC |
Output current | nom. | 10A |
Boost current 1 | max. | 12A / 300s |
Boost current 2 | max. | 15A / 60s |
Overload behaviour | Constant current + Intermittent mode (Hiccup) | |
Mains frequency | nom. | 50/60Hz |
Input voltage AC | nom. | 3x380 .. 500VAC (-10/+15%) |
Input voltage DC | nom. | 530 .. 675VDC (-15/+20%) |
Inrush current AC 1 | max. | 25 / 30A <3ms |
Inrush energy AC 1 | max. | 0.3 / 0.8A2s |
Inrush current DC 2 | max. | 39 / 47 / 60A <3ms |
Inrush energy DC 2 | max. | 1.1 / 1.5 / 2.3A2s |
Output power | nom. | 240W |
Boost power 1 | max. | 288W / 300s |
Boost power 2 | max. | 360W / 60s |
Power factor | typ. | 0.60 |
Conversion efficiency AC 1 | min. | 93.1 / 93.2% |
Power losses AC 1 | max. | 17.8 / 17.5W |
No-load consumption AC 1 | max. | 1.6 / 2.0W |
Conversion efficiency DC 2 | typ. | 94.7 / 94.8 / 94.5% |
Power losses DC 2 | typ. | 13.4 / 13.2 / 14.0W |
No-load consumption DC 2 | max. | 2.0 / 2.3 / 3.0W |
Service lifetime 1 | min. | 82,000 / 78,000hrs |
Service / Early life MTBF 3 | min. | 1.8M / 0.79M hrs |
Ambient operating temperature | max. | -25 .. +70°Camb (-13 .. +158°Famb) |
Ambient operating temperature | nom. | -25 .. +55°Camb (-13 .. +131°Famb) |
Power derating | min. | 2.4W/°Camb (1.33W/°Famb) |
Operating altitude | nom. | 3000mASL (9842ftASL) |
Operating altitude | max. | 6000mASL (19685ftASL) 4 |
Ingress protection degree | IP 20 | |
Radiated noise emission | Class B | |
Conducted noise emission | Class B | |
Width x Height x Depth | max. | 55 x 129 x 138.2mm (2 11/64 x 5 5/64 x 5 7/16 inch) |
Weight | 780g (1.72lb) | |
Certifications (CB, UL, UR) | IEC/EN/UL/CSA 61010-1, 61010-2-201, 62368-1 (Ed.3) |
DRB240-48-3-XX | ||
---|---|---|
Output voltage | nom. | 48VDC |
Adjustment range | nom. | 45.. 56VDC |
Output current | nom. | 5A |
Boost current 1 | max. | 6A / 300s |
Boost current 2 | max. | 7.5A / 60s |
Overload behaviour | Constant current + Intermittent mode (Hiccup) | |
Mains frequency | nom. | 50/60Hz |
Input voltage AC | nom. | 3x380 .. 500VAC (-10/+15%) |
Input voltage DC | nom. | 530 .. 675VDC (-15/+20%) |
Inrush current AC 1 | max. | 25 / 30A <3ms |
Inrush energy AC 1 | max. | 0.3 / 0.8A2s |
Inrush current DC 2 | max. | 39 / 47 / 60A <3ms |
Inrush energy DC 2 | max. | 1.1 / 1.5 / 2.3A2s |
Output power | nom. | 240W |
Boost power 1 | max. | 288W / 300s |
Boost power 2 | max. | 360W / 60s |
Power factor | typ. | 0.60 |
Conversion efficiency AC 1 | min. | 93.8 / 94% |
Power losses AC 1 | max. | 15.9 / 15.3W |
No-load consumption AC 1 | max. | 1.9 / 2.3W |
Conversion efficiency DC 2 | typ. | 95.1 / 95.1 / 94.9% |
Power losses DC 2 | typ. | 12.4 / 12.4 / 12.9W |
No-load consumption DC 2 | max. | 1.9 / 2.3 / 3.0W |
Service lifetime 1 | min. | 94,000 / 90,000hrs |
Service / Early life MTBF 3 | min. | 1.8M / 0.79M hrs |
Ambient operating temperature | max. | -25 .. +70°Camb (-13 .. +158°Famb) |
Ambient operating temperature | nom. | -25 .. +55°Camb (-13 .. +131°Famb) |
Power derating | min. | 2.6W/°Camb (1.44W/°Famb) |
Operating altitude | nom. | 3000mASL (9842ftASL) |
Operating altitude | max. | 6000mASL (19685ftASL) 4 |
Ingress protection degree | IP 20 | |
Radiated noise emission | Class B | |
Conducted noise emission | Class B | |
Width x Height x Depth | max. | 55 x 129 x 138.2mm (2 11/64 x 5 5/64 x 5 7/16 inch) |
Weight | 780g (1.72lb) | |
Certifications (CB, UL, UR) | IEC/EN/UL/CSA 61010-1, 61010-2-201, 62368-1 (Ed.3) |
DRB480-24-3-XX | DRB480-48-3-XX | DRB480-72-3-XX | ||
---|---|---|---|---|
Output voltage | nom. | 24VDC | 48VDC | 72VDC |
Adjustment range | nom. | 22.5.. 29VDC | 45.. 56VDC | 70.. 85VDC |
Output current | nom. | 20A | 10A | 6.7A |
Boost current | max. | 30A / 7s | 15A / 7s | 10A / 7s |
Overload behaviour | Constant current + Intermittent mode (Hiccup) | |||
Mains frequency | nom. | 50/60Hz | ||
Input voltage AC | nom. | 3x380 .. 500VAC (-10/+15%) | ||
Input voltage DC | nom. | 530 .. 675VDC (-15/+20%) | ||
Inrush current AC 1 | max. | 12A <2ms | ||
Inrush energy AC 1 | max. | 0.1A2s | ||
Inrush current DC 2 | max. | 12A <2ms | ||
Inrush energy DC 2 | max. | 0.1A2s | ||
Output power | nom. | 480W | ||
Boost power | max. | 720W / 7s | ||
Power factor | typ. | 0.92 | ||
Conversion efficiency AC 1 | min. | 95.1 / 94.9% | 95.3 / 95.1% | 95.7 / 95.6% |
Power losses AC 1 | max. | 24.7 / 25.8W | 23.7 / 24.7W | 21.6 / 22.1W |
No-load consumption AC 1 | max. | 3.0 / 3.2W | 3.0 / 3.3W | 3.0 / 3.3W |
Conversion efficiency DC 2 | typ. | 95.7 / 95.5 / 95.3% | 95.9 / 95.8 / 95.6% | 95.7 / 95.5 / 95.3% |
Power losses DC 2 | typ. | 21.6 / 22.6 / 23.7W | 20.5 / 21.0 / 22.1W | 21.6 / 22.6 / 23.7W |
No-load consumption DC 2 | max. | 3.1 / 3.3 / 3.8W | 3.0 / 3.3 / 3.9W | 3.1 / 3.4 / 4.0W |
Service lifetime 1 | min. | 148,000 / 124,000hrs | 157,000 / 119,000hrs | 137,000 / 123,000hrs |
Service / Early life MTBF 3 | min. | 0.86M / 0.48M hrs | 0.86M / 0.45M hrs | 0.86M / 0.45M hrs |
Ambient operating temperature | max. | -25 .. +70°Camb (-13 .. +158°Famb) | ||
Ambient operating temperature | nom. | -25 .. +55°Camb (-13 .. +131°Famb) | ||
Power derating | min. | 12W/°Camb (6.67W/°Famb) |
9.6W/°Camb (5.33W/°Famb) |
8.0W/°Camb (4.44W/°Famb) |
Operating altitude | nom. | 3000mASL (9842ftASL) | ||
Operating altitude | max. | 6000mASL (19685ftASL) 4 | ||
Ingress protection degree | IP 20 | |||
Radiated noise emission | Class B | |||
Conducted noise emission | Class B | |||
Width x Height x Depth | max. | 65 x 129 x 159.3mm (2 9/16 x 5 5/64 x 6 17/64 inch) |
||
Weight | 1050g (2.31lb) | |||
Certifications (CB, UL, UR) | IEC/EN/UL/CSA 61010-1, 61010-2-201, 62368-1 (Ed.3) |
DRB480-24-3-XX | ||
---|---|---|
Output voltage | nom. | 24VDC |
Adjustment range | nom. | 22.5.. 29VDC |
Output current | nom. | 20A |
Boost current | max. | 30A / 7s |
Overload behaviour | Constant current + Intermittent mode (Hiccup) | |
Mains frequency | nom. | 50/60Hz |
Input voltage AC | nom. | 3x380 .. 500VAC (-10/+15%) |
Input voltage DC | nom. | 530 .. 675VDC (-15/+20%) |
Inrush current AC 1 | max. | 12A <2ms |
Inrush energy AC 1 | max. | 0.1A2s |
Inrush current DC 2 | max. | 12A <2ms |
Inrush energy DC 2 | max. | 0.1A2s |
Output power | nom. | 480W |
Boost power | max. | 720W / 7s |
Power factor | typ. | 0.92 |
Conversion efficiency AC 1 | min. | 95.1 / 94.9% |
Power losses AC 1 | max. | 24.7 / 25.8W |
No-load consumption AC 1 | max. | 3.0 / 3.2W |
Conversion efficiency DC 2 | typ. | 95.7 / 95.5 / 95.3% |
Power losses DC 2 | typ. | 21.6 / 22.6 / 23.7W |
No-load consumption DC 2 | max. | 3.1 / 3.3 / 3.8W |
Service lifetime 1 | min. | 148,000 / 124,000hrs |
Service / Early life MTBF 3 | min. | 0.86M / 0.48M hrs |
Ambient operating temperature | max. | -25 .. +70°Camb (-13 .. +158°Famb) |
Ambient operating temperature | nom. | -25 .. +55°Camb (-13 .. +131°Famb) |
Power derating | min. | 12W/°Camb (6.67W/°Famb) |
Operating altitude | nom. | 3000mASL (9842ftASL) |
Operating altitude | max. | 6000mASL (19685ftASL) 4 |
Ingress protection degree | IP 20 | |
Radiated noise emission | Class B | |
Conducted noise emission | Class B | |
Width x Height x Depth | max. | 65 x 129 x 159.3mm (2 9/16 x 5 5/64 x 6 17/64 inch) |
Weight | 1050g (2.31lb) | |
Certifications (CB, UL, UR) | IEC/EN/UL/CSA 61010-1, 61010-2-201, 62368-1 (Ed.3) |
DRB480-48-3-XX | ||
---|---|---|
Output voltage | nom. | 48VDC |
Adjustment range | nom. | 45.. 56VDC |
Output current | nom. | 10A |
Boost current | max. | 15A / 7s |
Overload behaviour | Constant current + Intermittent mode (Hiccup) | |
Mains frequency | nom. | 50/60Hz |
Input voltage AC | nom. | 3x380 .. 500VAC (-10/+15%) |
Input voltage DC | nom. | 530 .. 675VDC (-15/+20%) |
Inrush current AC 1 | max. | 12A <2ms |
Inrush energy AC 1 | max. | 0.1A2s |
Inrush current DC 2 | max. | 12A <2ms |
Inrush energy DC 2 | max. | 0.1A2s |
Output power | nom. | 480W |
Boost power | max. | 720W / 7s |
Power factor | typ. | 0.92 |
Conversion efficiency AC 1 | min. | 95.3 / 95.1% |
Power losses AC 1 | max. | 23.7 / 24.7W |
No-load consumption AC 1 | max. | 3.0 / 3.3W |
Conversion efficiency DC 2 | typ. | 95.9 / 95.8 / 95.6% |
Power losses DC 2 | typ. | 20.5 / 21.0 / 22.1W |
No-load consumption DC 2 | max. | 3.0 / 3.3 / 3.9W |
Service lifetime 1 | min. | 157,000 / 119,000hrs |
Service / Early life MTBF 3 | min. | 0.86M / 0.45M hrs |
Ambient operating temperature | max. | -25 .. +70°Camb (-13 .. +158°Famb) |
Ambient operating temperature | nom. | -25 .. +55°Camb (-13 .. +131°Famb) |
Power derating | min. | 9.6W/°Camb (5.33W/°Famb) |
Operating altitude | nom. | 3000mASL (9842ftASL) |
Operating altitude | max. | 6000mASL (19685ftASL) 4 |
Ingress protection degree | IP 20 | |
Radiated noise emission | Class B | |
Conducted noise emission | Class B | |
Width x Height x Depth | max. | 65 x 129 x 159.3mm (2 9/16 x 5 5/64 x 6 17/64 inch) |
Weight | 1050g (2.31lb) | |
Certifications (CB, UL, UR) | IEC/EN/UL/CSA 61010-1, 61010-2-201, 62368-1 (Ed.3) |
DRB480-72-3-XX | ||
---|---|---|
Output voltage | nom. | 72VDC |
Adjustment range | nom. | 70.. 85VDC |
Output current | nom. | 6.7A |
Boost current | max. | 10A / 7s |
Overload behaviour | Constant current + Intermittent mode (Hiccup) | |
Mains frequency | nom. | 50/60Hz |
Input voltage AC | nom. | 3x380 .. 500VAC (-10/+15%) |
Input voltage DC | nom. | 530 .. 675VDC (-15/+20%) |
Inrush current AC 1 | max. | 12A <2ms |
Inrush energy AC 1 | max. | 0.1A2s |
Inrush current DC 2 | max. | 12A <2ms |
Inrush energy DC 2 | max. | 0.1A2s |
Output power | nom. | 480W |
Boost power | max. | 720W / 7s |
Power factor | typ. | 0.92 |
Conversion efficiency AC 1 | min. | 95.7 / 95.6% |
Power losses AC 1 | max. | 21.6 / 22.1W |
No-load consumption AC 1 | max. | 3.0 / 3.3W |
Conversion efficiency DC 2 | typ. | 95.7 / 95.5 / 95.3% |
Power losses DC 2 | typ. | 21.6 / 22.6 / 23.7W |
No-load consumption DC 2 | max. | 3.1 / 3.4 / 4.0W |
Service lifetime 1 | min. | 137,000 / 123,000hrs |
Service / Early life MTBF 3 | min. | 0.86M / 0.45M hrs |
Ambient operating temperature | max. | -25 .. +70°Camb (-13 .. +158°Famb) |
Ambient operating temperature | nom. | -25 .. +55°Camb (-13 .. +131°Famb) |
Power derating | min. | 8.0W/°Camb (4.44W/°Famb) |
Operating altitude | nom. | 3000mASL (9842ftASL) |
Operating altitude | max. | 6000mASL (19685ftASL) 4 |
Ingress protection degree | IP 20 | |
Radiated noise emission | Class B | |
Conducted noise emission | Class B | |
Width x Height x Depth | max. | 65 x 129 x 159.3mm (2 9/16 x 5 5/64 x 6 17/64 inch) |
Weight | 1050g (2.31lb) | |
Certifications (CB, UL, UR) | IEC/EN/UL/CSA 61010-1, 61010-2-201, 62368-1 (Ed.3) |
DRB960-24-3-XX | DRB960-48-3-XX | DRB960-72-3-XX | ||
---|---|---|---|---|
Output voltage | nom. | 24VDC | 48VDC | 72VDC |
Adjustment range | nom. | 22.5.. 29VDC | 45.. 56VDC | 70.. 85VDC |
Output current | nom. | 40A | 20A | 13.3A |
Boost current | max. | 60A / 7s | 30A / 7s | 20A / 7s |
Overload behaviour | Constant current + Intermittent mode (Hiccup) | |||
Mains frequency | nom. | 50/60Hz | ||
Input voltage AC | nom. | 3x380 .. 500VAC (-10/+15%) | ||
Input voltage DC | nom. | 530 .. 675VDC (-15/+20%) | ||
Inrush current AC 1 | max. | 13A <2ms | ||
Inrush energy AC 1 | max. | 0.1A2s | ||
Inrush current DC 2 | max. | 13A <2ms | ||
Inrush energy DC 2 | max. | 0.1A2s | ||
Output power | nom. | 960W | ||
Boost power | max. | 1440W / 7s | ||
Power factor | typ. | 0.94 | ||
Conversion efficiency AC 1 | min. | 95.2 / 95.1% | 95.9 / 95.8% | 96.3 / 96.2% |
Power losses AC 1 | max. | 48.4 / 49.5W | 41.0 / 42.1W | 36.9 / 37.9W |
No-load consumption AC 1 | max. | 6.1 / 6.0W | 6.2 / 6.1W | 5.6 / 5.6W |
Conversion efficiency DC 2 | typ. | 97.4 / 97.3 / 96.8% | 96.9 / 96.8 / 96.2% | 97.2 / 96.8 / 96.5% |
Power losses DC 2 | typ. | 25.6 / 26.6 / 31.7W | 30.7 / 31.7 / 37.9W | 27.7 / 31.7 / 34.8W |
No-load consumption DC 2 | max. | 6.1 / 6.9 / 6.8W | 5.8 / 7.0 / 6.6W | 5.6 / 6.5 / 6.4W |
Service lifetime 1 | min. | 117,000 / 113,000hrs | 130,000 / 128,000hrs | 130,000 / 124,000hrs |
Service / Early life MTBF 3 | min. | 0.97M / 0.39M hrs | ||
Ambient operating temperature | max. | -25 .. +70°Camb (-13 .. +158°Famb) | ||
Ambient operating temperature | nom. | -25 .. +55°Camb (-13 .. +131°Famb) | ||
Power derating | min. | 16W/°Camb (8.89W/°Famb) |
16W/°Camb (8.89W/°Famb) |
6.24W/°Camb (3.47W/°Famb) |
Operating altitude | nom. | 3000mASL (9842ftASL) | ||
Operating altitude | max. | 6000mASL (19685ftASL) 4 | ||
Ingress protection degree | IP 20 | |||
Radiated noise emission | Class B | |||
Conducted noise emission | Class B | |||
Width x Height x Depth | max. | 100 x 129 x 171.9mm (315/16 x 5 5/64 x 6 49/64 inch) |
||
Weight | 1750g (3.86lb) | |||
Certifications (CB, UL, UR) | IEC/EN/UL/CSA 61010-1, 61010-2-201, 62368-1 (Ed.3) |
DRB960-24-3-XX | ||
---|---|---|
Output voltage | nom. | 24VDC |
Adjustment range | nom. | 22.5.. 29VDC |
Output current | nom. | 40A |
Boost current | max. | 60A / 7s |
Overload behaviour | Constant current + Intermittent mode (Hiccup) | |
Mains frequency | nom. | 50/60Hz |
Input voltage AC | nom. | 3x380 .. 500VAC (-10/+15%) |
Input voltage DC | nom. | 530 .. 675VDC (-15/+20%) |
Inrush current AC 1 | max. | 13A <2ms |
Inrush energy AC 1 | max. | 0.1A2s |
Inrush current DC 2 | max. | 13A <2ms |
Inrush energy DC 2 | max. | 0.1A2s |
Output power | nom. | 960W |
Boost power | max. | 1440W / 7s |
Power factor | typ. | 0.94 |
Conversion efficiency AC 1 | min. | 95.2 / 95.1% |
Power losses AC 1 | max. | 48.4 / 49.5W |
No-load consumption AC 1 | max. | 6.1 / 6.0W |
Conversion efficiency DC 2 | typ. | 97.4 / 97.3 / 96.8% |
Power losses DC 2 | typ. | 25.6 / 26.6 / 31.7W |
No-load consumption DC 2 | max. | 6.1 / 6.9 / 6.8W |
Service lifetime 1 | min. | 117,000 / 113,000hrs |
Service / Early life MTBF 3 | min. | 0.97M / 0.39M hrs |
Ambient operating temperature | max. | -25 .. +70°Camb (-13 .. +158°Famb) |
Ambient operating temperature | nom. | -25 .. +55°Camb (-13 .. +131°Famb) |
Power derating | min. | 16W/°Camb (8.89W/°Famb) |
Operating altitude | nom. | 3000mASL (9842ftASL) |
Operating altitude | max. | 6000mASL (19685ftASL) 4 |
Ingress protection degree | IP 20 | |
Radiated noise emission | Class B | |
Conducted noise emission | Class B | |
Width x Height x Depth | max. | 100 x 129 x 171.9mm (315/16 x 5 5/64 x 6 49/64 inch) |
Weight | 1750g (3.86lb) | |
Certifications (CB, UL, UR) | IEC/EN/UL/CSA 61010-1, 61010-2-201, 62368-1 (Ed.3) |
DRB960-48-3-XX | ||
---|---|---|
Output voltage | nom. | 48VDC |
Adjustment range | nom. | 45.. 56VDC |
Output current | nom. | 20A |
Boost current | max. | 30A / 7s |
Overload behaviour | Constant current + Intermittent mode (Hiccup) | |
Mains frequency | nom. | 50/60Hz |
Input voltage AC | nom. | 3x380 .. 500VAC (-10/+15%) |
Input voltage DC | nom. | 530 .. 675VDC (-15/+20%) |
Inrush current AC 1 | max. | 13A <2ms |
Inrush energy AC 1 | max. | 0.1A2s |
Inrush current DC 2 | max. | 13A <2ms |
Inrush energy DC 2 | max. | 0.1A2s |
Output power | nom. | 960W |
Boost power | max. | 1440W / 7s |
Power factor | typ. | 0.94 |
Conversion efficiency AC 1 | min. | 95.9 / 95.8% |
Power losses AC 1 | max. | 41.0 / 42.1W |
No-load consumption AC 1 | max. | 6.2 / 6.1W |
Conversion efficiency DC 2 | typ. | 96.9 / 96.8 / 96.2% |
Power losses DC 2 | typ. | 30.7 / 31.7 / 37.9W |
No-load consumption DC 2 | max. | 5.8 / 7.0 / 6.6W |
Service lifetime 1 | min. | 130,000 / 128,000hrs |
Service / Early life MTBF 3 | min. | 0.97M / 0.39M hrs |
Ambient operating temperature | max. | -25 .. +70°Camb (-13 .. +158°Famb) |
Ambient operating temperature | nom. | -25 .. +55°Camb (-13 .. +131°Famb) |
Power derating | min. | 16W/°Camb (8.89W/°Famb) |
Operating altitude | nom. | 3000mASL (9842ftASL) |
Operating altitude | max. | 6000mASL (19685ftASL) 4 |
Ingress protection degree | IP 20 | |
Radiated noise emission | Class B | |
Conducted noise emission | Class B | |
Width x Height x Depth | max. | 100 x 129 x 171.9mm (315/16 x 5 5/64 x 6 49/64 inch) |
Weight | 1750g (3.86lb) | |
Certifications (CB, UL, UR) | IEC/EN/UL/CSA 61010-1, 61010-2-201, 62368-1 (Ed.3) |
DRB960-72-3-XX | ||
---|---|---|
Output voltage | nom. | 72VDC |
Adjustment range | nom. | 70.. 85VDC |
Output current | nom. | 13.3A |
Boost current | max. | 20A / 7s |
Overload behaviour | Constant current + Intermittent mode (Hiccup) | |
Mains frequency | nom. | 50/60Hz |
Input voltage AC | nom. | 3x380 .. 500VAC (-10/+15%) |
Input voltage DC | nom. | 530 .. 675VDC (-15/+20%) |
Inrush current AC 1 | max. | 13A <2ms |
Inrush energy AC 1 | max. | 0.1A2s |
Inrush current DC 2 | max. | 13A <2ms |
Inrush energy DC 2 | max. | 0.1A2s |
Output power | nom. | 960W |
Boost power | max. | 1440W / 7s |
Power factor | typ. | 0.94 |
Conversion efficiency AC 1 | min. | 96.3 / 96.2% |
Power losses AC 1 | max. | 36.9 / 37.9W |
No-load consumption AC 1 | max. | 5.6 / 5.6W |
Conversion efficiency DC 2 | typ. | 97.2 / 96.8 / 96.5% |
Power losses DC 2 | typ. | 27.7 / 31.7 / 34.8W |
No-load consumption DC 2 | max. | 5.6 / 6.5 / 6.4W |
Service lifetime 1 | min. | 130,000 / 124,000hrs |
Service / Early life MTBF 3 | min. | 0.97M / 0.39M hrs |
Ambient operating temperature | max. | -25 .. +70°Camb (-13 .. +158°Famb) |
Ambient operating temperature | nom. | -25 .. +55°Camb (-13 .. +131°Famb) |
Power derating | min. | 6.24W/°Camb (3.47W/°Famb) |
Operating altitude | nom. | 3000mASL (9842ftASL) |
Operating altitude | max. | 6000mASL (19685ftASL) 4 |
Ingress protection degree | IP 20 | |
Radiated noise emission | Class B | |
Conducted noise emission | Class B | |
Width x Height x Depth | max. | 100 x 129 x 171.9mm (315/16 x 5 5/64 x 6 49/64 inch) |
Weight | 1750g (3.86lb) | |
Certifications (CB, UL, UR) | IEC/EN/UL/CSA 61010-1, 61010-2-201, 62368-1 (Ed.3) |
All products are available as -A0 (screw terminal) and -A1 (push-in terminal) versions.
Unless otherwise stated, all values are specified in normal mounting position, at full load, nominal input and output voltages, 25°C ambient temperature and a run-in time of 5 minutes.
1 400 / 500VAC
2 540 / 650 / 800VDC
3 Telcordia SR-332 Issue 4
4 not UL approved, reduced OVC
DOWNLOADS & LINKS
Product Brochure | |
---|---|
DIN-Rail Power Solutions Brochure |
EU & UK Declaration of Conformity | |
---|---|
EU RoHS Declaration of Conformity | |
EAC Registration | |
TSCA | |
California Proposition 65 |
REACH | China RoHS | |
---|---|---|
DRB120-12-3-XX | ||
DRB120-24-3-XX | ||
DRB240-24-3-XX | ||
DRB240-48-3-XX | ||
DRB480-24-3-XX | ||
DRB480-48-3-XX | ||
DRB480-72-3-XX | ||
DRB960-24-3-XX | ||
DRB960-48-3-XX | ||
DRB960-72-3-XX |
61010 Certificate | 61010 Report | |||
---|---|---|---|---|
UL | CB | UL | CB | |
DRB120-XX-3-XX | ||||
DRB240-XX-3-XX | ||||
DRB480-XX-3-XX | ||||
DRB960-XX-3-XX |
62368 Certificate | 62368 Report | |||
---|---|---|---|---|
UL | CB | UL | CB | |
DRB120-XX-3-XX | ||||
DRB240-XX-3-XX | ||||
DRB480-XX-3-XX | ||||
DRB960-XX-3-XX |
With our many years of experience and our extensive knowledge of customer applications in the power supply industrial market, we are your #1 partner.
TDK Group's emphasis is on quality and reliability, and we perform extensive testing on the components we use and manufacture the products in our own factories worldwide. This gives us full control over the process, allowing us to achieve incomparable quality.
Through our global sales network, you can obtain our DIN-Rail products worldwide.
How about a conversation?
Whatever the demands of your application, whatever the production run, we're here to help. Give us a brief description of your needs and we'll be in touch.